RE –102 RE - 104 Fire Alarm Control Panel Installation, Commissioning & Operating Manual

Pagina 2

P/N RE - 102 / 104 Rev. No. 0 92.2 Specification AC Power 220 VAC, 50 Hz. +10% - 15% Battery (Lead Acid only) Charging: Constant Voltage – 27.

Pagina 3

P/N RE - 102 / 104 Rev. No. 0 102.3 Controls and Indication 2.3.1 LED Indication System On – Green A.C Power On – Green Standby On – Gree

Pagina 4

P/N RE - 102 / 104 Rev. No. 0 11RESET Key: This key is pressed to reset the entire system and While in reset condition, all detector loop voltages

Pagina 5 - Table of Contents

P/N RE - 102 / 104 Rev. No. 0 12Chapter 3: Installation 3.1 Installation Precaution Installation Precautions WARNING - Several different sou

Pagina 6 - Chapter 1: Introduction

P/N RE - 102 / 104 Rev. No. 0 13 Verify that wire sizes are adequate for all initiating and Indicating device loops. Most d

Pagina 7 - 1.4 User Responsibility

P/N RE - 102 / 104 Rev. No. 0 14 3.2 Mounting Details Place the panel in its mounting position and fix the panel to the wal

Pagina 8 - 1.5 Routine Testing

P/N RE - 102 / 104 Rev. No. 0 15 3.3 Input Circuits The control panel has 2 / 4 zone input circuits depending on the variant. The maximum loop r

Pagina 9 - 2.1 Product Features

P/N RE - 102 / 104 Rev. No. 0 163.4 Output Circuits Sounder Circuits: The RE - 102 / 104 provides Notification Appliance Circuits standard as Cla

Pagina 10 - 2.2 Specification

P/N RE - 102 / 104 Rev. No. 0 17Chapter 4: Operating Instruction 4.1 Switch Functions SILENCE Key: This key is used in Fire / Fault

Pagina 11

P/N RE - 102 / 104 Rev. No. 0 18MENU Key: The MENU key is used to enter into the programming mode for changing the zone status and other settings.

Pagina 12 - 2.4 Mechanical Construction

P/N RE - 102 / 104 Rev. No. 0 1

Pagina 13 - Chapter 3: Installation

P/N RE - 102 / 104 Rev. No. 0 194.3 Operation 4.3.1 ZONE FAULT RESPONSE: When faults like Open/ Short occurred in the loop, the corresponding ZON

Pagina 14

P/N RE - 102 / 104 Rev. No. 0 202. By silencing, sounders are switched off and Fire relay output for actuators will remains in ON Condition until

Pagina 15

P/N RE - 102 / 104 Rev. No. 0 214.3.5.1. Zone 1 From this menu, the zone 1 loop can configured as enable, disable, Zone test and Walk test. The d

Pagina 16

P/N RE - 102 / 104 Rev. No. 0 22This feature helps to perform the testing of devices by a single person. In this mode if the zone detects any fir

Pagina 17

P/N RE - 102 / 104 Rev. No. 0 234.3.5.4. Zone 4 From this menu, the zone 4 loop can configured as enable, disable, Zone test and Walk test. The d

Pagina 18

P/N RE - 102 / 104 Rev. No. 0 244.3.5.8. Silence Time The Silence time will be enabled only when the Auto silence is ‘Enabled’. If the Auto Silen

Pagina 19 - 1. Zone 1

P/N RE - 102 / 104 Rev. No. 0 25Chapter 5: Servicing 5.1 Walk Test Mode: The RE - 102 / 104 provides the capability to perform a walktest of the

Pagina 20

P/N RE - 102 / 104 Rev. No. 0 26 5.2 Installation/Replacement of PCB: Remove the screws of PCB, which has to be changed and remove the PCB from t

Pagina 21 - MENU KEY - FLOW DIAGRAM

P/N RE - 102 / 104 Rev. No. 0 27Chapter 6: Battery Calculation Normal Condition : X = S (Amps) x ____ Hrs. (Backup time required) Alarm Cond

Pagina 22 - <Enabled>

P/N RE - 102 / 104 Rev. No. 0 28Chapter 7: Trouble Shooting Indication Root Cause Remedy There is no indication

Pagina 23 - 3. Zone 3

P/N RE - 102 / 104 Rev. No. 0 2

Pagina 24 - 4. Zone 4

P/N RE - 102 / 104 Rev. No. 0 29Chapter 8: Terminal Details

Pagina 25 - Password

P/N RE - 102 / 104 Rev. No. 0 30RAVEL ELECTRONICS PVT. LTD No. 150-A, Elec. Indsl. Estate, Perungudi, chennai – 600 096. India Tel.: 24961004 / 24

Pagina 26 - Chapter 5: Servicing

P/N RE - 102 / 104 Rev. No. 0 31 RAVEL ELECTRONICS PVT. LTD No. 150-A, Elec. Indsl. Estate, Perungudi, chennai – 600 096. India Tel.: 24961004 / 2

Pagina 27

P/N RE - 102 / 104 Rev. No. 0 32 Ravel Electronics Pvt Ltd., 150A, Electronic Industrial Estate, Perungudi, Chennai – 60

Pagina 28

P/N RE - 102 / 104 Rev. No. 0 3NOTES:

Pagina 29 - Chapter 7: Trouble Shooting

P/N RE - 102 / 104 Rev. No. 0 4Table of Contents CHAPTER 1: Introduction …………...……...4 1.1: System Design & Planning...

Pagina 30

P/N RE - 102 / 104 Rev. No. 0 5Chapter 1: Introduction This manual is intended as a complete guide to the RE - 102 / 104 model Conventional Fire

Pagina 31 - RAVEL ELECTRONICS PVT. LTD

P/N RE - 102 / 104 Rev. No. 0 6 1.3 Fire Alarm Procedures In accordance with IS 2189: 1999, written procedures should be laid down for dealing wi

Pagina 32 - WARRANTY CERTIFICATE

P/N RE - 102 / 104 Rev. No. 0 7 1.5 Routine Testing In order to ensure that the system is fully operational, and to comply with the requirements o

Pagina 33 - Ravel Electronics Pvt Ltd.

P/N RE - 102 / 104 Rev. No. 0 8Chapter 2: Product Description The RE - 102 / 104 is a 2 / 4 zone microprocessor based conventional Fire Alarm Con